Putting into Service
20
168779 / 854960300010
2011-09-23·BA00·III·en·02
Load and Motor Switch, Load-Break
Switch 8549/1
8.4 Back-Up Fuse
Provide suitable back-up fuses, see chapter 5 "Technical Data".
9
Putting into Service
Before commissioning
Check if cables and lines are clamped properly.
Check the torques.
Ensure that the connection has been correctly made.
Ensure that all screws and nuts are fully tightened.
10 Maintenance
10.1 Regular maintenance work
Consult the relevant regulations (e.g. IEC/EN 60079-17) to determine the type and
extent of inspections.
Plan the intervals so that any defects in the equipment which may be anticipated are
promptly detected.
Separate plugs and sockets at regular intervals to prevent contact corrosion
To check as part of the maintenance schedule:
X
Check if the cables are clamped properly.
X
Check that cable entries are tight
X
Check the state of the cable entries
X
Check the seals for damage.
X
Inspect the device for signs of visible damage.
X
Compliance with the permitted temperatures in accordance with IEC/EN 60079-0.
X
Make sure that the device is used according to its designated use
WARNING
Risk due to unauthorised work being performed on the device!
Risk of injury and damage to equipment.
Assembly, installation, commissioning and servicing work must only be performed by
personnel who are both authorised and suitably trained for this purpose.
WARNING
Danger from energised parts!
Risk of severe injuries.
All connections and wiring must be disconnected from the power supply.
Secure the connections against unauthorised activation.
WARNING
Short-circuit in the main circuit
Contacts may be damaged.
Replace the switch after each short circuit in the main circuit (the element
is hermetically sealed and the state of the switching contacts cannot be
checked).
Summary of Contents for 8549/1
Page 2: ......
Page 3: ...Betriebsanleitung Last und Motorschalter Lasttrennschalter 8549 1...
Page 26: ...168779 854960300010 2011 09 23 BA00 III de 02...
Page 27: ...Operating Instructions Load and Motor Switch Load Break Switch 8549 1...
Page 50: ...168779 854960300010 2011 09 23 BA00 III en 02...
Page 51: ......
Page 52: ...168779 854960300010 2011 09 23 BA00 III de en 02...