168779 / 854960300010
2011-09-23·BA00·III·en·02
Assembly
15
Load and Motor Switch, Load-Break
Switch 8549/1
7.5 Mount the Switch on the Mounting Plate
Single switch
Fasten the switch on the mounting plate by means of 4 screws M5 with 1.8 Nm.
Two switches with parallel drive
Plug the left switch vertically on the dovetails of the right switch.
Fasten the switch on the mounting plate by means of 6 screws M5 with 1.8 Nm.
7.6 Mount the Parallel Drive
12440E00
Fig. 7-9: Mounting the parallel drive
Before installation of the parallel drive (1), make sure that both switches are in zero
position.
Place the parallel drive (1) and the washers (2) on the selector shafts of the switch, as
shown in fig. 7-9.
Tighten the nuts M6 (3) with 4.5 Nm.
7.7 Mount the Enclosure Cover with Actuator Insert
Place the enclosure cover with mounted actuator insert vertically on the enclosure/
shaft.
Tighten the mounting screws of the enclosure cover.
WARNING
Risk due to loose conductors!
The connected wires of the mounted auxiliary contacts are located near the parallel
drive.
Lay the wires in a way that they do not come into contact with the parallel drive!
1
2
3
Summary of Contents for 8549/1