168779 / 854960300010
2011-09-23·BA00·III·en·02
Assembly
11
Load and Motor Switch, Load-Break
Switch 8549/1
Two switches with parallel drive
Fig. 7-2: Drill pattern for two switches with parallel drive
Drill 6 threaded holes M5 in the mounting plate.
7.2 Mounting a PE Terminal and/or N Terminal (Option)
12434E00
Fig. 7-3: Installation of the terminal on the left side of the switch
Installation of the terminal on the left side of the switch
Attach the PE terminal or N terminal (1) on the dovetail (2) from the top.
Insert the cover (3) from the left side until it engages into the cover of the switch (4).
Fasten the cover by means of 2 mounting screws (5) and tighten them with 2.5 Nm on
the terminal.
When drilling the assembly holes, always observe the centre of the selector
shaft of the parallel drive (Z).
12433E00
1)
Assembly holes 8549/1, 3 pole
2)
Assembly holes 8549/1, 3 pole + N or 3 pole + PE terminal
An N terminal and/or a PE terminal can be optionally mounted on the
switch 8549/1, 3 pole.
A PE terminal can be optionally mounted on the switch 8549/1, 3 pole.
Z
77
1)
112
)
M5
140
1
2
3
4
5