Assembly
12
168779 / 854960300010
2011-09-23·BA00·III·en·02
Load and Motor Switch, Load-Break
Switch 8549/1
Installation of the terminal on the right side of the switch
Place the switch (4) on the dovetail of the PE terminal or the N terminal (1) from the top.
Insert the cover (3) from the right side until it engages in the cover of the switch.
Fasten the cover by means of 2 mounting screws (5) and tighten them with 2.5 Nm on
the terminal.
7.3 Mounting the Auxiliary Contact (Option)
12435E00
Fig. 7-4: Mounting the auxiliary contact
Carefully remove the cover (1) of the mounting slot (3) using a screwdriver or a knife.
Carefully insert the auxilary contact (2) into the mounting slot until it engages.
Paste the circuit diagram indicating the respective switching function to the rating plate
of the switch.
Before mounting an auxiliary contact, the cover must be removed.
The IP protection of the switch, IP20 (finger touch-safe), remains active even
if the cover is removed.
The switching function of the auxiliary contact depends on the mounting slot
used (left-hand: delayed (ON), advanced (OFF); right: synchronising).
1
3
2
CLICK