What to do if the measuring system breaks

If the measuring system is destroyed, i.e., if the expansion liquid escapes, the pressure 

in the membrane will drop and permanently opens the circuit of the temperature controller 

and temperature limiter. The temperature limiter can no longer be unlocked.

What to do if the temperature is below normal

If the sensor of the temperature controller or limiter has cooled down to temperatures  

below approx. -20 °C (-65 °C at TU = -60 °C), the electric circuit opens, however, it closes 

automatically again if temperature rises.

10

Maintenance and repair

10.1 Maintenance

• Consult the relevant national regulations to determine the type and extent  

of inspections.

• Adapt inspection intervals to the operating conditions.

During maintenance of the device, check at least:

• whether the clamping screws holding the electric lines are securely seated,

• whether the device enclosure and / or protective enclosure have cracks or other visible 

signs of damage,  

• whether the permissible ambient temperatures are observed,

• whether the device is used according to its designated use.

WARNING

Risk of electric shock or malfunctioning of the device due to unauthorized 

work!

Non-compliance can result in severe injuries and material damage.

• Work performed on the device must only be carried out by appropriately 

authorized and qualified electricians.

Summary of Contents for 8146/5041 Series

Page 1: ...N EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Operating instructions Additional languages www stahl ex com EN Double temperature controller and limiter Series 8146 5041 8146 5...

Page 2: ...4 2 3 Symbols on the device 5 3 Safety notes 5 3 1 Operating instructions storage 5 3 2 Safe use 5 3 3 Modifications and alterations 5 4 Function and device design 5 4 1 Function 6 5 Technical data 6...

Page 3: ...942 943 0 Fax 49 7942 943 4333 Internet www stahl ex com E Mail info stahl de 1 2 Information regarding the operating instructions ID No 240634 8146662300 Publication Code 2016 07 11 BA00 III en 02 Ha...

Page 4: ...NOTICE Type and source of danger damage Consequences of danger Taking countermeasures to avoid the danger damage Symbol Meaning Tips and recommendations on the use of the device General danger Danger...

Page 5: ...ance overhaul repair may only be carried out by appropriately authorized and trained personnel During installation and operation observe the information characteristic values and rated operating condi...

Page 6: ...ntact is activated due to temperature related volume changes In case of leakage of the measuring system the temperature controller switches off permanently Temperature controller If the temperature of...

Page 7: ...n be switched via contact path 1 2 The contact path 1 4 is used for signalling purposes NC terminal 1 2 NO terminal 1 4 AC 400 V 16 A AC 400 V 6 3 A AC 230 V 16 A AC 230 V 6 3 A AC 400 V 16 A AC 400 V...

Page 8: ...r lock Standard with captive M6 stainless steel combo head screws Mounting Installation Cable glands 1 x M20 x 1 5 cable entry Clamping range 4 13 mm Connection type 5 x spring clamp terminals Connect...

Page 9: ...ient temperature NC terminal 1 2 NO terminal 1 4 AC 400 V 16 A AC 400 V 2 A AC 230 V 16 A AC 230 V 2 A AC 400 V 16 A AC 400 V 2 A AC 230 V 25 A AC 230 V 2 A NC terminal 1 2 NO terminal 1 4 AC 400 V 16...

Page 10: ...to IEC EN 60695 UL 94 ASTM D635 Seal Standard foamed silicone Special EPDM 20 80 C Sensor stainless steel VA 1 4571 AISI 316L Cover lock Standard with captive M6 stainless steel combo head screws Moun...

Page 11: ...Carry out installation strictly according to the instructions and national safety and accident prevention regulations to maintain the explosion protection Select and install the electrical device so...

Page 12: ...tool used to fasten the cable gland Adjust the hole diameters to the dimensions of the built in parts and or their seals Measure the dimensions on the plane surfaces of the inner side of the enclosur...

Page 13: ...to incorrectly laid cables in the Ex e enclosure Non compliance results in severe or fatal injuries Adhere to the required creepage distances and clearances Fasten mounting rails or elements properly...

Page 14: ...ation voltage value is at least 1500 V doubled sum of the rated operational voltage of intrinsically safe circuits plus 1000 V WARNING Risk of electric shock short circuit due to incorrectly dimension...

Page 15: ...inal bridging is only permitted if original Ex accessories are used If necessary retrofit required partitions For additional splice protection use core end sleeves or cable lugs Make sure that the cro...

Page 16: ...d in accordance with IEC EN 61439 and not connected to PE After completing the electric installation the following operations must be performed Install protection against accidental contact Set the tr...

Page 17: ...o the desired limit temperature allow at least 5 minutes for temperature to equalize while measuring and monitoring the exact temperature on the temperature sensor with a calibrated comparison measuri...

Page 18: ...e electric circuit opens however it closes automatically again if temperature rises 10 Maintenance and repair 10 1 Maintenance Consult the relevant national regulations to determine the type and exten...

Page 19: ...damp cloth use water or mild non abrasive non scratching cleaning agents Do not use aggressive detergents or solvents WARNING Danger of electric shock due to energised parts Non compliance can result...

Page 20: ...arding disposal Separate materials when sending it for recycling Ensure environmentally friendly disposal of all components according to the statutory regulations 13 Accessories and Spare parts NOTE M...

Reviews: