240634 / 8146662300
2016-07-11·BA00·III·en·02
Operation
17
(Double) temperature controller and
limiter
Series 8146/5041, 8146/5051
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
8.1
Adjustment of temperature controller
Setpoint adjustment of temperature controller
Adjustments of limiting values for temperature limiter
• A functional test is reequired, according to the relevant regulations, e.g. 94/9 EG.
Setting the limit value according to the scale
• Set the limit value on the setpoint adjuster above the scale.
• Secure the setting by sealing the setpoint adjuster
(e.g. using a temperature-resistant screw locking varnish).
Setting the limit value according to the operation-specific properties of the system
• Heat the temperature sensor - inside the system - to the desired limit temperature
(allow at least 5 minutes for temperature to equalize), while measuring and monitoring
the exact temperature on the temperature sensor with a calibrated comparison
measuring instrument.
• Determine the desired switching point position by rotating the setpoint adjuster from
the scale value toward the initial scale value (open circuit 1 ... 2 and close circuit 1 ... 4).
For the temperature limiter, the setpoint adjuster must be additionally sealed (e.g. using
a temperature-resistant screw locking varnish)
9
Operation
Depending on the ambient conditions, the following situations can occur during operation
Unlocking the temperature limiter
After the value has dropped by about 10% below the set limit value, the temperature
limiter can be unlocked.
16648E00
• Adjust the desired setpoint on
the temperature scale using
a screwdriver.
16649E00
• Manually push the release bolt in until
it snaps into place (refer to opposite
drawing).
• The temperature limiter is unlocked.