Floodlight LED
Series 6125
7.3.2 Electrical connections
Electrical connection
Observe the maximum clamping possibility of the connection terminals
(see "Technical data" section).
Observe the following when connecting to the electrical connection:
• Clamping must be carried out precisely.
• Do not clamp any part of the conductor insulation.
• Do not mix up the conductors.
• Observe the technical regulations when connecting the conductor.
• Clamp the conductor firmly.
Connection terminals
Through wiring of the mains supply connection
Standard:
Spring clamp terminals
Optional:
Spring clamp terminals
Clamping range:
0.75 to 4 mm
2
solid and
finely stranded
(2 free clamping units
per pole available)
Clamping range:
0.75 to 4 mm
2
finely and
extra finely stranded
0.75 to 6 mm
2
solid
(2 free clamping units
per pole available)
Stripping length:
10 to 11 mm
Stripping length:
13 to 15 mm
15516E00
18616E00
Through wiring with 2.5 mm
2
cross section for max. 12 A.
N
L1
L2
L3
L3
L2
L1
N
L1, L2, L3
= phase
N
= neutral conductor
PE
= protective
conductor