Floodlight LED
Series 6125
7.3.3 Cable entries
The standard luminaire is delivered with 2 lead-in holes, 1 cable gland and
1 stopping plug.
Tightening torques for components from R. STAHL Schaltgeräte GmbH
Luminaires with installed cable entries and stopping plugs from
R. STAHL Schaltgeräte GmbH must be tightened using the following values:
Luminaires with cable entries and stopping plugs which are not supplied by
R. STAHL Schaltgeräte GmbH
Please observe the following:
• the required dust resistance!
• the required type of protection!
• the required temperature resistance!
• the IP degree of protection according to the rating plate!
• the operating instructions of the cable entries and stopping plugs!
• the required tightening torques!
• the range of the permissible cable diameter!
• Insert the metal cable entries and/or stopping plugs into the PE!
Tightening torque
Connection thread
Pressure screw
Cable entry
8161
M20 x 1.5
2.3 Nm
1.5 Nm
M25 x 1.5
3.0 Nm
2.0 Nm
Stopping plugs
8290
M20 x 1.5
1.0 Nm
–
M25 x 1.5
1.5 Nm
–
DANGER
Explosion hazard due to impermissible cable entries and stopping plugs!
Non-compliance results in severe or fatal injuries.
• Only use separately certified cable glands and stopping
plugs which have been tested and certified according to
Directive 2014/34/EU (ATEX) or IECEx (CoC) and which comply
with the standard version stated in the certificate of the luminaire.