3.5 UPS Settings
Parameter 3
Parameter 1
Parameter 2
There are three parameters to set up the UPS.
Parameter 1: Program alternatives. Refer to below table.
Parameter 2 and Parameter 3 are the setting options or values
for each program.
01: Output voltage setting
Interface
Setting
For 110/115/120/127 VAC models:
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
127: presents output voltage is 127Vac
For 208/220/230/240 VAC models:
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac
(Default)
240: presents output voltage is 240Vac
02: Programmable outlets enable/disable
Interface
Setting
ENA: Programmable outlets enable (Default)
DIS: Programmable outlets disable
03: Programmable outlets setting
Interface
Setting
Setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode.