Page | 18
3.6 Steps for setting programmable outlet
Step 1:
Before entering setting mode, the UPS should be in Stand-by
mode (off-charging) and make sure the battery is connected. The
LCD display is shown as right.
Step 2:
Press and hold the
“Selection” button for 3 seconds to enter
Setting mode.
Step 3:
Press the “Up“ button (ON/MUTE) to switch to "02" of program
list. Then press “Enter“ button to enter value setting of parameter
2. Press the “Up” button to change the value to “ENA” to enable
the programmable outlet function. Then press “Enter” button
again to confirm the setting.
Step 4:
Press the “Up“ button (ON/MUTE) again to switch to "03" of
program list. Then press “Enter“ button for setting programmable
outlet time. Push “Up” button to change the value of backup time
according your demand. Then press “Enter” to confirm the
setting.
Step 5:
Press “Up“ button (ON/MUTE) to switch to "00" of program list.
Then press “Enter” button to exit setting menu
.
Step 6:
Disconnect AC input and wait until the LCD display is off. The new setting will be activated when
turning on the UPS again.