13
1. Outlet Turn On After UPS On
–
select the time to automatically enable
this outlet within the specified time when the UPS is powered
on. If “0”
sec is selected, the outlet will be enabled once the UPS is powered on
.
2. Outlet Turn Off After AC Failure
–
select this option to automatically
disable the outlet within the specified time after utility outage to shed the
less critical loads to provide longer battery back-up time for the other
more critical loads connected to the UPS.
3. Outlet Turn On After AC Recovery
–
select this option to automatically
enable the outlet within the specified time after the utility is restored.
4. Outlet Turn Off When Battery Low -
select this option to automatically
disable the outlet at the specified remaining battery power capacity(%)
during battery mode to shed the less critical loads to prolong battery
back-up time for the other more critical loads connected to the UPS.
5. Outlet Turn Off When UPS Overload
–
select this option to automatically
disable the outlet during overload condition (bypass mode) to possibly
allow the more critical loads:
a) To be continually supplied via Bypass without shut down
6. You have to select the "Setting" menu to configure new
parameters. The calibration is confirmed successfully after the UPS
beeps twice. Turn off the UPS and unplug input power cord from AC
Power Utility receptacle to shutdown whole unit without internal power
supply existing, after setting is complete. 3 seconds later reconnect input
power cord into AC Power Utility receptacle and turn on the UPS,
referring to the section 4.4 Operation. The UPS will perform in new
settings.
7. Manual Control Switch
– Click “On” or “Off” to manually enabled or
disabled the programmable outlets, overriding all previous settings
.
Summary of Contents for UniStar C
Page 1: ...Form No 003 2308 Rev C 1K 2K 3K UniStar C Intelligent True On Line UPS User Manual ...
Page 9: ...8 3 2 Rear Panel Descriptions 120V 1KVA 10 8 7 1 2 3 5 4 6 2KVA 3KVA ...
Page 19: ...18 4 3 Set up Tower Configuration Setup Step 1 Power Module Battery Module Step 1 ...
Page 20: ...19 Rack Mount Configuration Setup Step 1 Step 2 Step 3 ...
Page 21: ...20 Step 4 Step 5 ...
Page 27: ...26 Q1 Q2 R1 R2 S ...
Page 28: ...27 T U1 U2 U3 V ...
Page 32: ...31 4 4 3 Battery Replacement Step 1 Step 2 ...
Page 33: ...32 Step 3 Step 4 1KVA 2K 3KVA ...