37
Fig 5.5
2. The UPS Bypass loop is also equipped with overload protection. Its overload
capacity is illustrated by the graph & table below.
5.5 Inverter Failure
Output Load short circuit when being supplied from inverter
If the output load is shorted while being supplied by the Inverter, the UPS will
shutdown the Inverter automatically. The Fault LED lights up and the audio
alarm beeps continuously. The UPS will not switch on automatically after a
short circuit condition is eliminated. The UPS has to be re-start manually (refer
to 4.4
.1 „Start Up in Normal Mode‟).