Current Crest Factor
3:1
Harmonic Distortion
≦
3% THD(Linear Load)
≦
7% THD(Non-Linear Load)
Transient
Response(ms)
<=
60ms/5%
Waveform
Pure Sine wave
Efficiency
To AC Mode (Full load)
85%
85%
88%
To Battery Mode (Full
load)
83%
83%
85%
Battery System
Type
12V/7.2Ah
12V/7.2Ah
12V/9Ah
Numbers of Batteries
3
6
6
Backup Time(Full Load)
>7min.
>7min.
>5min.
Recharging Time
4 Hours to 90%
Charging Current (Max.)
1.1A
2.16A
2.7A
Charging Voltage
41.0Vdc±0.5V
82.0Vdc±0.5V
82.0Vdc±0.5V
Hot Swappable Battery
Yes
Internal battery
Yes
DC leakage current
30uA ( 10uA) with no AC applied and the unit in the off
position
Battery type
Sealed, non-spill, maintenance-free, lead acid
Transfer Time
AC to DC
Zero
Inverter to Bypass
2.5ms(Typical)
Zero
DC Start
Yes
Self Diagnostics
By button of the front panel or Software Control
Front Panel
LCD
Load Level/Battery Level/ Battery Mode/ Normal Mode/Bypass
Mode/ Self-Test/ Weak/Bad Battery/Site Wiring Fault/ Fault/
Overload/Programmable Outlet1//Programmable Outlet2
Key
ON Button/ OFF Button/ (Test/Alarm Reset Button)
Protection
Overload
(AC Mode )
<
105
%
continuous
>
106
%~
120
%
for 30 seconds transfer to bypass
>
121
%~
150
%
for 10 seconds transfer to bypass
>
150
%
for immediately transfer to bypass
*
Notification: continuous alarm.
Summary of Contents for UniStar C
Page 1: ...Form No 003 2308 Rev C 1K 2K 3K UniStar C Intelligent True On Line UPS User Manual ...
Page 9: ...8 3 2 Rear Panel Descriptions 120V 1KVA 10 8 7 1 2 3 5 4 6 2KVA 3KVA ...
Page 19: ...18 4 3 Set up Tower Configuration Setup Step 1 Power Module Battery Module Step 1 ...
Page 20: ...19 Rack Mount Configuration Setup Step 1 Step 2 Step 3 ...
Page 21: ...20 Step 4 Step 5 ...
Page 27: ...26 Q1 Q2 R1 R2 S ...
Page 28: ...27 T U1 U2 U3 V ...
Page 32: ...31 4 4 3 Battery Replacement Step 1 Step 2 ...
Page 33: ...32 Step 3 Step 4 1KVA 2K 3KVA ...