Voltage:
Voltage at motor must be not more than 10% above or below motor name-
plate rated voltage or motor may overheat, causing overload tripping and re-
duced component life. If voltage is less than 90% or more than 110% of rated
voltage when motor is running at full load, consult power company.
TABLE I - RECOMMENDED WIRING DATA 60 HZ 115V MOTORS
Dist in Ft. (M) - Service to Motor
Model
Motor
0-100
101-200
201-300
Temp.
No.
H.P.
(0-30)
(31-60)
(61-90)
Rating-°C
JTACL-AA
1/2
14 (2.0)
12 (3.0)
10 (5.0)
75
JTADL-2A
14 (2.0)
12 (3.0)
10 (5.0)
75
JTADL-AA
3/4
14 (2.0)
10 (5.0)
8 (7.0)
75
JTAEL-AA,-2A
1
14 (2.0)
10 (5.0)
8 (7.0)
75
JTAFL-2A
1-1/2
12 (3.0)
8 (7.0)
6 (13.0)
75
TABLE II - RECOMMENDED CIRCUIT BREAKER SIZES 60 Hz 115V MOTORS
Model
Motor
Full Load
Branch Circuit Breaker
No.
H.P.
(amps)
Rating (amps)
JTACL-AA
1/2
7.0
15
JTADL-AA
3/4
9.2
15
JTADL-2A
3/4
9.0
15
JTAEL-AA
1
11.2
15
JTAEL-2A
1
12.0
15
JTAFL-2A
1-1/2
16
20
TABLE III - RECOMMENDED CIRCUIT BREAKER SIZES
60 Hz, 220V and 230V MOTORS
Model
Motor
Voltage/
Full Load
Branch Circuit Breaker
No.
H.P.
Hz/Ph
(amps)
Rating (amps)
JTAD-230A
3/4
230/60/1
4.8
15
JTAE-230A
1
230/60/1
6.1
15
JTADL-220AA
3/4
220/60/1
5.1
15
JTAEL-220AA
1
220/60/1
6.24
15
NOTICE:
For distances up to 300 ft. (90m), service to motor,
use #14 AWG (2mm
2
) wire rated at 75°C.
Air Switch:
Models with -AA suffix are equipped with air switch control. Use WC17-57
Button and WC17-58 tubing or equivalent (available separately).
NOTICE:
If motor does not respond to air switch, length of tubing may need
adjustment. Maximum recommended tubing length is 15' (4.6m). Different
buttons may require shorter lengths of tubing. Make sure no kinks exist in
tubing.