Table 2: Diagnostic function of the process guard locking
Function
Input
Safety sensor
Input
Solenoid control
Feedback
Magnetic flux
measurement
LEDs
Diagnos-
tic output
Note
IN 1
IN 2
Green
Red
Blue
OUT 1
1 Voltage supply OK
0 V
0 V
not activated
f l a s h e s
1x
off
off
0 V
Input circuit IN 1 not available
2 Ready for operation
24 V
0 V
not activated
on
off
off
1X
pulsing
Ready for activation of the guard locking
3
Guard locking with typical
locking force
24 V
24 V
activated
off
off
on
24 V
Min. 1200 N locking force existing
4
Guard locking with typical
locking force
0 V
24 V
activated
off
off
f l a s h e s
1x
2x pulsing Min. 1200 N locking force existing
5 Locking force not reached
24 V
24 V
activated
off
off
f l a s h e s
2x
3x pulsing Locking force of 900 N not reached
*2)
6 Locking force not reached
24 V
24 V
not activated
off
on
off
4x pulsing
Magnetic flux interrupted when throw
open the door
*1)
7 Error force measurement
24 V
24 V
activated
off
f l a s h e s
1x
off
5x pulsing
Error in the magnetic flux measure-
ment
*1)
8 Error reed contact
24 V
24 V
x
off
f l a s h e s
2x
off
6x pulsing
Error in the magnetic flux measure-
ment
*1)
*1)
If this error is detected, the device will lock electronically and a standard error ac-
knowledgment is not possible any more. In order to acknowledge this error, the device
has to be disconnected from the power supply after removal of the cause of the error.
*2)
If this error is detected, the device will lock electronically. In order to acknowledge
this error, the input IN 2 has to be switched off.
Note:
If several errors are detected, the first error remains in a pending state until
the errors have been eliminated.