SMART CELLAR INVERTER COOLING UNIT
5. The use of thread sealant paste is required for flared union and flare nut threads.
●
The use of thread sealant should not be installed on the flare face or mating surface, this will
cause contamination in the refrigeration system, this is classed as a non condensable.
●
Recommended thread sealant
●
Leak lock
●
Loxea
NOTICE:
Field installed refrigeration copper line sets must be rated for R410a refrigerant as a minimum.
Connect the Outdoor Unit Electrical Wire
1. Remove the wire clip, connect the power connection cord and signal control cord to the wiring
terminal according to the colour depicted.
2. Fix the power connection cord and signal control cord with the wire clip.
NOTICE:
●
After tightening the screws, gently pull the power cord and power connection cord to ensure
they are firmly secure.
●
Never cut the power connection cord to either decrease or increase the distance of the cord.
●
Connecting the DRED Module
1. For the connection wire and power cable of the DRED module, it is recommended to use
insulated cable that meets IEC 57 of IEC 60245.
2. If the power cable and connection wire are unsuitable for outdoor use, the power cable and
connection wire should be installed in conduit to protect against rain and ultra-violet rays.
3. The DRED module should be installed indoors or inside an enclosed space that prevents rain
and ultra-violet rays.
4. The connection wires for the DRED module, indoor unit and outdoor unit should use the same
wire clamp. The other wire clamps are used for the power cable and connection wires of
another indoor unit and outdoor unit.