Waukesha Cherry-Burrell
Installation and Operation
April 2008
95-03083
Page 9
Solenoids Operation
Barrel-Type Solenoid
•
24VDC (5-25VDC) typically used on all valves
•
Up to three (3) solenoids
•
Ports in the base are numbered
•
On single-seat valves, the air boost requires two (2)
solenoids
•
120VAC (50-60Hz) solenoid is available
Solenoid Operation
Solenoids direct compressed air through the ports in the
base of the control top to drive the motion of the valve. For
the solenoid to work correctly and achieve the required
valve condition, specific ports must be open or plugged.
Many configurations are possible. Figure 5 and Figure 6
list the appropriate configurations for W60/W80/W90 and
W70 valves. Prior to startup, perform a functional test on
each valve by applying compressed air.
W60 / W80 / W90 Single Seat Solenoid and Port Arrangements
W70 Series Mix Proof and W75RS PMO Solenoid and Port Arrangements
Figure 5: Single Seat Solenoid Arrangements W60/W80/W90
Figure 6: Solenoid Arrangements, W70 Series Mix Proof and W75RS PMO Mix Proof
Single Seat - No Solenoid - AR
Plug
Plug
Plug
Plug Plug Plug Plug Plug Plug Vent Open Plug
Single Seat - No Solenoid - AL & AA
Plug
Plug
Plug
Plug Plug Plug Open Plug Plug Vent Plug Plug
Single Seat - 1 Solenoid - AR
Solenoid
Plug
Plug
Open Plug Plug Plug Plug Plug Vent Open Open
Single Seat - 1 Solenoid - AL
Solenoid
Plug
Plug
Plug Plug Plug Plug Vent Plug Open Plug Open
Single Seat - 2 Solenoids - Air Boost & AA
Solenoid
Solenoid
Plug
Open Plug Plug Plug Plug Vent Open Plug Open
Single Seat 3 Pos. AR - 2 Solenoid
Solenoid
Solenoid
Plug
Open Open Plug Plug Plug Plug Vent Open Open
Note:
For W60 / W80 / W90 single seat valves:
AR = Air to raise actuator, AL = Air to lower actuator, AA = Air to air actuator
AR (2) Solenoids: Solenoid 1 = AR; Solenoid 2 = Air boost
AL (2) Solenoids: Solenoid 1 = Air boost; Solenoid 2 = AL
3-Position AR Actuator (2) Solenoids: Solenoid 1 = Valve open; Solenoid 2 = M id-position
VA10 0 -58 5
Valve Configuration
Solenoid
Location
1
Solenoid
Location
2
S olenoid
Location
3
Port
1
Port
2
Port
3
Port
4
Top
Port
In
Port
Port
5
Port
6
Port
8
M ix Proof - No Solenoid
Plug
Plug
Plug
Plug Plug Plug Plug Plug Plug Vent Open Plug
M ix Proof - 1 Solenoid
Solenoid
Plug
Plug
Open Plug Plug Plug Plug Plug Vent Open Open
Solenoid
Solenoid
Plug
Open Open Plug Plug Plug Plug Vent Open Open
M ix Proof - 3 Solenoids
Solenoid
Solenoid
Solenoid Open Open Open Plug Plug Plug Vent Open Open
M ix Proof Radial Seal (RS) - No Solenoid
Plug
Plug
Plug
Plug Plug Plug Plug Plug Plug Open Plug Plug
M ix Proof Radial Seal (RS) - 1 Solenoid
Solenoid
Plug
Plug
Open Plug Plug Plug Plug Plug Open Plug Open
M ix Proof Radial Seal (RS) - 2 Solenoids
Solenoid
Solenoid
Plug
Open Open Plug Plug Plug Plug Open Plug Open
M ix Proof Radial Seal (RS) - 3 Solenoids
Solenoid
Solenoid
Solenoid Open Open Open Plug Plug Plug Open Plug Open
PMO - No Solenoid
Plug
Plug
Plug
Plug Plug Plug Open Plug Plug Open Open Plug
PMO - 1 Solenoid
Solenoid
Plug
Plug
Open Plug Plug Open Plug Plug Open Open Open
PMO - 2 Solenoids
Solenoid
Solenoid
Plug
Open Open Plug Open Plug Plug Open Open Open
PMO - 3 Solenoids
Solenoid
Solenoid
Solenoid Open Open Open Open Plug Plug Open Open Open
Note:
For all W-S eries Mix Proof:
Solenoid 1 = Valve Open; Solenoid 2 = Upper seat lift; Solenoid 3 = Lower seat lift
M ix Proof - 2 Solenoids
Valve Configuration
S olenoid
Location
1
S olenoid
Location
2
S olenoid
Location
3
Port
1
Port
2
Port
3
Port
4
Top
Port
In
Port
VA10 0 -58 6
Port
5
Port
6
Port
8