Marley
/
MD
Cooling Tower
/
Engineering Data : Schematic
9
NOTE
1
Use this bulletin for preliminary layouts only
. Obtain
current drawings from your Marley sales representative. All
table data is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley
UPDATE
web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia. M connection located on the side of the tower. A 3" M
drain connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H
A
Weight/Cell
Heaviest
Section
MD5008MAC2L
165
5.5
80
3526
2413
3072
1723
891
MD5008MLC2L
165
5.5
79
MD5008NAC2L
179
7.5
81
MD5008NLC2L
179
7.5
79
MD5008PAC2L
202
11
81
MD5008PLC2L
202
11
80
MD5008QAC2L
217
15
81
MD5008QLC2L
217
15
80
MD5008MAD2L
180
5.5
80
3831
2718
3197
1848
957
MD5008MLD2L
180
5.5
79
MD5008NAD2L
196
7.5
81
MD5008NLD2L
196
7.5
79
MD5008PAD2L
222
11
81
MD5008PLD2L
222
11
80
MD5008QAD2L
239
15
81
MD5008QLD2L
239
15
80
MD5008MAF2L
188
5.5
80
4136
3023
3323
1974
1083
MD5008MLF2L
188
5.5
79
MD5008NAF2L
205
7.5
81
MD5008NLF2L
205
7.5
79
MD5008PAF2L
234
11
81
MD5008PLF2L
234
11
80
MD5008QAF2L
251
15
81
MD5008QLF2L
251
15
80
MD5008 MULTICELL
Summary of Contents for Cooling Tower Marley MD
Page 1: ...Marley MD CoolingTower Engineering Data Specifications...
Page 2: ......