Marley
/
MD
Cooling Tower
/
Engineering Data: Support
22
D
E
E
CL ANCHOR
BOLT
CL
ANCHOR
BOLT
OVERALL OF BASIN
L
C
C L
AN
CHOR
BOL
T
C L
AN
CHOR BOL
T
W
OV
ER
ALL WIDTH OF
B
ASIN
HOLES FOR
M16 ANCHOR
BOLTS
4 REQD
21
21
TOWER COLLECTION
BASIN
A
SUPPORTING STEEL
SINGLE CELL
NORMAL
GAUGE
21
SUPPORT
BY OTHERS
TOWER
COLLECTION
BASIN
VIEW A
Model
Dimensions
Design
Operating
Weight
per cell
kg
Design
Operating Load
at support beam
kg/m
W
L
C
D
E
F
MD5008__C
2578
2731
2537
2629
51
165
3072
563
MD5008__D
2578
2731
2537
2629
51
165
3197
586
MD5008__F
2578
2731
2537
2629
51
165
3323
609
MD5010__C
2578
3651
2537
3550
51
165
3906
549
MD5010__D
2578
3651
2537
3550
51
165
4069
568
MD5010__F
2578
3651
2537
3550
51
165
4256
592
MD5016__C
3607
3651
3566
3397
127
318
5860
908
MD5016__D
3607
3651
3566
3397
127
318
6143
951
MD5016__F
3607
3651
3566
3397
127
318
6375
982