Marley
/
MD
Cooling Tower
/
Engineering Data : Schematic
15
NOTE
1
Use this bulletin for preliminary layouts only
. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley
UPDATE
web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia.
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H
A
Weight/Cell
Heaviest
Section
MD5016PAC1L
317
11
79
4239
2529
5805
3225
1710
MD5016PLC1L
320
11
78
MD5016QAC1L
345
15
80
MD5016QLC1L
348
15
79
MD5016RAC1L
369
18.5
80
MD5016RLC1L
372
18.5
79
MD5016SAC1L
390
22
81
MD5016SLC1L
394
22
80
MD5016PAD1L
350
11
79
4544
2834
6089
3508
1763
MD5016PLD1L
353
11
78
MD5016QAD1L
383
15
80
MD5016QLD1L
384
15
79
MD5016RAD1L
410
18.5
80
MD5016RLD1L
412
18.5
79
MD5016SAD1L
436
22
81
MD5016SLD1L
437
22
80
MD5016TAD1L
475
30
82
MD5016TLD1L
471
30
80
MD5016PAF1L
368
11
79
4848
3139
6320
3739
1977
MD5016PLF1L
370
11
78
MD5016QAF1L
403
15
80
MD5016QLF1L
401
15
79
MD5016RAF1L
431
18.5
80
MD5016RLF1L
431
18.5
79
MD5016SAF1L
460
22
81
MD5016SLF1L
459
22
80
MD5016TAF1L
500
30
82
MD5016TLF1L
493
30
80
MD5016 SINGLE CELL