Marley
/
MD
Cooling Tower
/
Engineering Data : Schematic
17
NOTE
1
Use this bulletin for preliminary layouts only
. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley
UPDATE
web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia.
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H
A
Weight/Cell
Heaviest
Section
MD5016PAC2L
317
11
79
4547
2837
5860
3279
1710
MD5016PLC2L
320
11
78
MD5016QAC2L
345
15
80
MD5016QLC2L
348
15
79
MD5016RAC2L
369
18.5
80
MD5016RLC2L
372
18.5
79
MD5016SAC2L
390
22
81
MD5016SLC2L
394
22
80
MD5016PAD2L
350
11
79
4852
3142
6143
3563
1800
MD5016PLD2L
353
11
78
MD5016QAD2L
383
15
80
MD5016QLD2L
384
15
79
MD5016RAD2L
410
18.5
80
MD5016RLD2L
412
18.5
79
MD5016SAD2L
436
22
81
MD5016SLD2L
437
22
80
MD5016TAD2L
475
30
82
MD5016TLD2L
471
30
80
MD5016PAF2L
368
11
79
5156
3447
6375
3794
2032
MD5016PLF2L
370
11
78
MD5016QAF2L
403
15
80
MD5016QLF2L
401
15
79
MD5016RAF2L
431
18.5
80
MD5016RLF2L
431
18.5
79
MD5016SAF2L
460
22
81
MD5016SLF2L
459
22
80
MD5016TAF2L
500
30
82
MD5016TLF2L
493
30
80
MD5016 TWO OR THREE CELL