Function
Display name
Use
Choice span
Hart
®
polling
address
ADDRESS
Hart®
polling
address
modification.
0 ÷ 15
The minimum
polling time is
8ms
Transmitter
information
INFO
The polling address, the
lower sensor limit (LSL), the
upper sensor limit (USL) and
the firmware revision are
shown.
-
Password
setting
PASSWORD
Allows to insert a new
password for the transmitter.
To be used with care.
0000 ÷ 9999
Expert
command:
Manual zero
elevation
ZERO ELEV.
(disabled in
volumetric
flow meters
mode)
Manual
zero
elevation
insertion.
6 digits,
including “–“
sign and
decimal point
Expert
command:
Heavier
specific gravity
HEAVIER SG
Manual
heavier
specific
gravity insertion
0.1 ÷
displacer
density
Expert
command:
Gas or liquid
lighter specific
gravity
LIGHTER SG
Manual
lighter
specific
gravity insertion
0.0 ÷
(
HEAVIER SG
– 0.1)
Factory setting
restore
RESTORE
Select and confirm using
buttons
and [OK].
-
I
NFORMATION
!
The password is in 4 digits format and spans from 0000 to 9999. If you can’t
remember or find the password you set, please contact our technical department.