The electronic transmitters have some configuration functions available via keyboard and LCD
display, provided with the transmitters themselves.
Press the [MENU] button to enter the password entering dialog (the default password is
0000). Confirm by [OK] to enter the configuration menu.
The display will allow to choose from the different functions described in the table below.
Use the
and
buttons to show the sequence of the available functions and press [OK] to
confirm the selected function.
When the display is in numerical entering mode, the cursor will blink.
To move the cursor press the
button; to raise the value of the digit press the
button.
Press the [OK] button to confirm; use instead the [MENU] button to cancel the modifications
and to go back to the standard display.
Function
Display name
Use
Choice span
Zero setting
LRV
Measure linked to the zero
and to the 4mA output. The
measuring unit is shown in
the lower right corner of the
display
Between the
sensor limits
Full span
setting
URV
Measure linked to the full
span and to the 20mA
output. The measuring unit is
shown in the lower right
corner of the display
Between the
sensor limits
Measuring unit
selection
PV UNIT
(disabled in
volumetric
flow meters
mode)
Measuring unit selection from
the available ones. Press
o
to scroll.
Level
(Interface)
:
%, m, in, cm,
mm
Density
Kg/l
Sensor
Temperature
unit
TEMP.UNIT
Temperature unit selection
from the available ones.
Press
o
to scroll.
°C, °K, °F
Configuration
of the
measuring unit
typology
XFR FUNC
Selection of the measuring
unit typology (LINEAR or
DENSITY)
LINEAR
DENSITY