SPM Instrument AB
• Box 504 • SE-645 25 Strängnäs • Sweden
Technical data are subject to change without notice.
Tel +46 152 225 00 • Fax +46 152 15075 • [email protected] • www.spminstrument.com
ISO 9001:2000 certified © SPM 2017-09. 71947 B
28
Technical specifications
General
Vibration monitoring:
1 channel
Shock pulse monitoring:
1 channel
Analog outputs (4):
4 - 20 mA analog signal, selective range, no galvanic separation
Main relay (1):
250 V AC, 5A, 1250 VA
Secondary relays (4):
125 V AC, 1A, 60 VA / 150 V DC, 1A, 30 W
Power supply:
230 V AC, 115 V AC ±10% *
Power consumption:
max. 6 VA
Operating temperature range: 0 to 50 °C (32 to 122 °F)
Relative humidity:
max. 95%
Altitude:
up to 2000 m
Casing:
polycarbonate/PVC, IP65
TNC connector:
silver plated brass, 10 to 15 μ
Display screen:
LCD, 4 x 16 characters, back-lighted
Status display:
green, yellow, red LED
Dimensions:
200 x 144 x 77 mm
Weight:
1140 g
Machine Guard MG4-REF11A
* Please note: The type of power supply is selected on ordering. It is factory set and cannot be
changed by the user. Please check the unit label for data.
Summary of Contents for Machine Guard MG4-REF11A
Page 2: ......