Reset to default values:
• Hold down the invisible RESET button and press SET
to restore default parameters
Invisible RESET
button
REF11A
VIB 1.5 mm/s
SPM 40 %
Reset default parameters
An unmarked button is located in the space below the RIGHT and to the right of the DOWN but-
ton. Pressing SET while holding down this invisible RESET button restores the default parameters.
The message ”Def. init.” (default initiation) is displayed while the reset takes place. These are the
default settings:
SPM channel:
Working point: ............... 30%
TLT Alarm: ...................... relay 5
A1 (max): ....................... 70%, relay 1
A2 (min): ........................ 10%, relay 2
Analogue out: ................. 1 [ % ]
Analogue out: ................ 2 [ dBsv ] absolute
value of dBc
Analogue out: ................ 3 [ dBsv ] absolute
value of dBm
4 mA: .............................. 0 [dBsv]
Alarm delay: .................... – – –
General:
Password......................... ON
Measuring ....................... ON
TLT .................................. ON
Relays ............................. NC
VIB channel:
Measuring time ............... 1sec
Machine class .................. 3
TLT Alarm ....................... relay 5
A1 (max): ...................... 11.3 [mm/s], relay 3
A2 (min): ......................... 0.5 [mm/s], relay 4
Analogue out: ................. 4 [mm/s]
20mA: ............................. 50.0 [mm/s]
Alarm delay: .................... – – –