IM-P145-02
ST Issue 2
7
Temperature
°
C
Pressure bar g
Steam
saturation
curve
A
C
B
The product
must not
be used in this region.
The product should not be used in this region as damage to the internals may occur.
A
-
B
Flanged PN16, PN25, ASME 300, screwed and socket weld.
A
-
C
Flanged ASME 150.
Note:
Tri-clamp compatible end connections, used for hygienic / sanitary applications, are
only available on the FTS14-4.5.
Body design conditions
PN25
PMA Maximum allowable pressure
25 bar g @ 50
°
C
(25 psi g @ 122
°
F)
TMA Maximum allowable temperature
300
°
C
(572
°
F)
Minimum allowable temperature
-20
°
C
(-4
°
F)
Maximum operating pressure
A
-
B
19 bar g
(275.5 psi g)
PMO for saturated steam service
A
-
C
13.5 bar g
(195.5 psi g)
TMO Maximum operating temperature
225
°
C @ 19 bar g (437
°
F @ 275.5 psi g)
Minimum operating temperature
0
°
C
(32
°
F)
Note:
For lower operating temperatures consult Spirax Sarco
Maximum
FTS14-4.5
4.5 bar
(65 psi)
PMX
differential
FTS14-10
10 bar
(145 psi)
pressure
FTS14-14
14 bar
(203 psi)
Designed for a maximum cold hydraulic test pressure of: 37.5 bar g
(544 psi g)
2.4 Materials
Part Material
Body and cover
Austenitic stainless steel (316)
EN 10213-4 (1.4408)
ASTM A351 CF8M
Cover bolts
Stainless steel
BS EN 3506 A2-70
Cover gasket
Reinforced exfoliated graphite
'O' ring
Viton (FDA approved)
Internals
Stainless steel
*
2.2 Sizes and pipe connections
½", ¾" and 1"
Screwed BSP (BS 21 and DIN 2999) or NPT (ASME B 1.20.1)
½", ¾" and 1"
Socket weld ends to ASME B 16.11, BS 3799 Class 3000 or DIN 3239
DN15, 20 and 25
Flanged ends to ASME B 16.5 Class 150 and 300 or EN 1092-1/PN16/25
½", ¾" and 1"
Tri-clamp ends (FTS14-4.5 only).
Note:
For alternative connections please consult Spirax Sarco.
2.3 Pressure / temperature limits
(ISO 6552)
Summary of Contents for FTS14