IM-P145-02 

 ST Issue 2

11

Table 1  Recommended tightening torques

 Item  Part 

or 

N m 

(lbf ft)

  

 

mm

 2 

Cover bolts 

M10 x 30 

20 - 25 

(15 - 18)

 5 

Main valve seat 

17 A / F 

 

50 - 55 

(37 - 40)

 7 

Main valve assembly screws 

Pozidrive 

M4 x 6 

2.5 - 3.0  (1.8 - 2.2)

 9 

Air vent assembly 

17 A / F 

 

50 - 55 

(37 - 40)

 10 

SLR assembly, gasket and seal 

19 A / F 

 

35 - 40 

(25 - 30)

 17 

Sensor blanking plug 

11 A / F 

 

15 - 20 

(11 - 15)

The spare parts available are shown in heavy outline. Parts drawn in broken line are not 

supplied as spares.

Available spares

Maintenance kit 

3

5

(2 off), 

(2 off),

 8

9

12

14

16 

(1" only), 

18

Gasket set (packet of 3) 

3

15

How to order spares

 

Always order spares by using the description given in the column headed 'Available spares' and 

state the size, type of trap and pressure range i.e. 4.5, 10 or 14 bar.

Example:

 1 - Maintenance kit for a Spirax Sarco 

½

" FTS14-4.5 steam trap. 

7. Spare parts

16

15

Section of the main valve assembly 

- size DN25 (1") only.

Fig. 5

Main valve assembly

*Note:

 Item 

16

 is required for 1" size only

8

Steam lock 

release

assembly

14

16

12

7

5

6

3

6

9

Air vent assembly

10 + 13

15

18

11

2

Not available 

as a spare

Summary of Contents for FTS14

Page 1: ...duct information 3 Installation 4 Commissioning 5 Operation 6 Maintenance 7 Spare parts Copyright 2014 Printed in GB FTS14 Austenitic Stainless Steel Ball Float Steam Trap DN15 to 1 DN25 Installation and Maintenance Instructions IM P145 02 ST Issue 2 1452050 2 ...

Page 2: ...IM P145 02 ST Issue 2 2 ...

Page 3: ... or condensate which is in Group 2 of the above mentioned Pressure Equipment Directive The products use on other fluids may be possible but if this is contemplated Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered ii Check material suitability pressure and temperature and their maximum and minimum values If the maximum operating limits ...

Page 4: ...trols or alarms Ensure isolation valves are turned on and off in a gradual way to avoid system shocks 1 7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure Consider double isolation double block and bleed and the locking or labelling of closed valves Do not assume that the system has depressurised even when the pressure gauge indicates zero 1 8 Tempera...

Page 5: ...ature of the product may reach temperatures in excess of 400 C 752 F Many products are not self draining Take due care when dismantling or removing the product from an installation refer to Maintenance instructions 1 14 Freezing Provision must be made to protect products which are not self draining against frost damage in environments where they may be exposed to temperatures below freezing point ...

Page 6: ... down configurations Standards This product fully complies with the requirements of the European Pressure Equipment Directive 97 23 EC Certification This product is available with certification to EN 10204 3 1 Note All certification inspection requirements must be stated at the time of order placement Optional extras FTS14X is available with an integral strainer screen to protect the internals fro...

Page 7: ...bar g 437 F 275 5 psi g Minimum operating temperature 0 C 32 F Note For lower operating temperatures consult Spirax Sarco Maximum FTS14 4 5 4 5 bar 65 psi PMX differential FTS14 10 10 bar 145 psi pressure FTS14 14 14 bar 203 psi Designed for a maximum cold hydraulic test pressure of 37 5 bar g 544 psi g 2 4 Materials Part Material Body and cover Austenitic stainless steel 316 EN 10213 4 1 4408 AST...

Page 8: ... Although the standard flow configuration is right to left R L the connection orientation can be changed on site by undoing the four cover bolts and moving the cover to the preferred flow orientation Note A new gasket must always be fitted Warning The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully 3 7 Traps should ...

Page 9: ...nternals 3 11 Float traps should be fitted as close as possible to the outlet of the plant to be drained otherwise the trap can steam lock Steam locking occurs when the pipe between the condensate outlet and the steam trap fills with steam preventing the condensate from reaching the trap This can lead to system waterlogging which will affect plant efficiency It is very similar to the air locking e...

Page 10: ...to the DN25 1 traps only Refit the pivot frame 12 by tightening the assembly set screws 7 to the recommended torque see Table 1 Replace float assembly 8 and pivot pin 14 Fit a new O ring 15 onto the body ensuring that the O ring contact surfaces are all clean and in good condition Care must be taken to ensure that the O ring is not damaged during assembly A suitable lubricant may be used to ease a...

Page 11: ... line are not supplied as spares Available spares Maintenance kit 3 5 6 2 off 7 2 off 8 9 12 14 16 1 only 18 Gasket set packet of 3 3 15 How to order spares Always order spares by using the description given in the column headed Available spares and state the size type of trap and pressure range i e 4 5 10 or 14 bar Example 1 Maintenance kit for a Spirax Sarco FTS14 4 5 steam trap 7 Spare parts 16...

Page 12: ...IM P145 02 ST Issue 2 12 ...

Reviews: