![Spirax Sarco DLV7 Installation And Maintenance Instructions Manual Download Page 9](http://html1.mh-extra.com/html/spirax-sarco/dlv7/dlv7_installation-and-maintenance-instructions-manual_1347915009.webp)
IM-P204-03
CH Issue 8
9
2.5 Pressure / temperature limits - WS4 / WS4-3
The product
must not
be used in this region.
Body design conditions
PN25
Maximum design pressure
25 bar g @ 120
°C
Maximum design temperature
225
°C @ 21 bar g
Minimum design temperature
0
°C
Maximum operating pressure for saturated steam
21 bar g
Maximum operating temperature
225
°C @ 21 bar g
Minimum operating temperature
0
°C
Note:
For lower operating temperatures consult Spirax Sarco
Maximum differential pressure
25 bar g
Designed for a maximum cold hydraulic test pressure of
40 bar g
Note:
With internals fitted, test pressure must not exceed
25 bar g
Pressure bar g
Te
mp
er
at
ure
°C
Steam
saturation
curve
Summary of Contents for DLV7