![Spirax Sarco DLV7 Installation And Maintenance Instructions Manual Download Page 21](http://html1.mh-extra.com/html/spirax-sarco/dlv7/dlv7_installation-and-maintenance-instructions-manual_1347915021.webp)
IM-P204-03
CH Issue 8
21
B
C
Replace the guide plate and screw the new head set onto the stem (hand tight). Then
proceed to tighten by holding the nut
B
using a 22 mm A / F spanner and tighten the
head adaptor nut
C
with a 24 mm A / F spanner to a torque of 15 ±1 N m for the DN15
- DN20 and 20 ±2 N m for the DN25 - DN100.
Caution:
to prevent any damage care
must be taken not to twist the bellows. To prevent over-extension (stretching) of the
bellows locate the guide plate on the head set before tightening the plug to the stem.
When replacement of the head set is complete, remove nuts
A
and
B
.
14
13
Fit the guide plate and screw the head set onto the stem. Ensure the guide plate locates
over the head set. Hand tighten.
Summary of Contents for DLV7