Pressurised Thermophysical deaerator with operator manual for the control unit
In detail for the operating cycle of the deaerator:
Block of the DG feedwater valve when one of the following alarms occurs:
-
analogue DG level transmitter error
-
maximum DG level
Block the DG pressure and temperature control valves when one of the following alarms occurs:
-
analogue DG temperature transmitter error
-
analogue DG pressure transmitter error
-
analogue DG level transmitter error
-
minimum DG level
Pressing the emergency button during automatic operation will stop the cycle: all active functions will be
cancelled and the corresponding alarm will be activated.
To resume automatic operation set the emergency button in stand-by position and press the START button:
the cycle will restart.