IM-P537-01
EMM Issue 1
45
Pressurised Thermophysical deaerator with operator manual for the control unit
Fig.13
Pressing the Plant Parameters icon, Fig.13 will appear.
To change the page, press the
icon
To change any value, just press
on it: a keyboard will appear.
To confirm the new value, press
RET
Set the value of Δ LEVEL PV <
SV STOP PUMP always lower
than the value of Δ LEVEL PV <
SV START PUMP, otherwise the
pump will never start; by setting
Δ LEVEL PV < SV STOP PUMP
to "0" and Δ LEVEL PV < SV
START PUMP higher than "0"
the pump will always stop when
the set point Level is reached;
by setting both values to "0" the
pump will continue to run.
Press the
icon to return
to Fig.5.