6.4.7 OUTPUT sub-menu
Allows the selection of the type of measurement to be performed.
OUTPUT
DRIVE
OUTPUT
CLEAN
OUTPUT
COMMS
Sets Modbus address baud rate and infrared master / slave
configuration, and verifies the number of units on the IR bus.
See OUTPUT COMMS sub-menu.
0 or 4 mA, set, or check. Allows mA output signal to be selected,
referenced to specific TDS levels, and adjusted if required.
See OUTPUT - RETRANS notes.
Sets the probe cleaning cycle duration, interval, and pulsed or
constant. Removes / softens probe scaling.
After a leaning cycle, the process variable will not be updated
for 20 seconds this allows any bubbles on the probe to disperse.
Selects standard or pulsed. Standard (valve remains open during
blowdown cycle – default). Pulsed – valve open 10 seconds, closed
20 seconds. Pulsed prevents the water level from falling too quickly
in a small boiler, which could cause a low water alarm.
OUTPUT
RETRANS