IM-P403-89
EMM Issue 8
67
10.8.4 OUTPUT MENU
CLEAN - DRIVE (Action on blowdown / solenoid valve)
Ranges
STANDARD or PULSED - 10 sec open, 20 sec closed
Default
STANDARD
CLEAN - DURATION (Time to clean probe)
Ranges
0 – 99 seconds or 0 – 9 seconds (If purge time > 0)
Default
20 (9 seconds (If purge time > 0))
Resolution (steps)
1
Units
Seconds
CLEAN - INTERVAL (Time between probe cleaning)
Only available if CLEAN - DURATION is greater than 0 seconds.
Ranges
1 – 99
Default
12
Resolution (steps)
1
Units
Hours
CLEAN
Only available if CLEAN - DURATION is greater than 0 seconds.
Ranges
PULSED - 1 second on, 1 second off, or CONSTANT
(for CP32 already fitted with a pulse circuit)
Default
PULSED
RETRANS – 0 or 4 mA (Lowest output signal)
Ranges
0 mA or 4 mA
Default
4 mA
Units
mA
RETRANS – SET – 0 / 4 mA (Set PV to correspond to 0 or 4 mA)
Ranges
0 – FSD
Default
0
Resolution (steps)
0.1% FSD
Units
µS / cm or ppm