Thermo 230 / 231 / 300 / 301 / 350
6 Functional Checkouts
603
6.3.4 Igniter Box Check
NOTE
The igniter box may also be tested using the PC heater
diagnosis (component test).
WARNING
High voltage; 20.000 volts arcing across the igniter
electrodes.
CAUTION
Do not apply voltage to igniter box without electrodes.
Check
–
apply 24 V as shown on figure
–
normal condition: spark between electrodes.
6.3.5 Fuel Pump Check
6.3.5.1 Fuel Pump Check on Heaters with Control Unit
1572
A test gauge is required for performing the test. Such a
gauge (with a range from 0 to 15 bar) can be procured
from your authorized
Spheros
dealer.
The fuel pump and the fuel hoses must be replaced every
5 years.
CAUTION
The electronic ignition coil must be removed for safety
reasons.
Check
–
remove igniter box (refer to 9.2.7.1).
–
remove nozzle.
–
screw on tester.
–
cover flame sensor.
–
switch on heater.
–
after approximately 13 sec. pump pressure is
indicated (refer to diagram).
–
switch off heater.
–
unscrew tester.
CAUTION
Do not damage nozzle bore.
–
screw in nozzle and torque with 20 Nm.
–
install igniter box (refer to 9.2.7.2).
Igniter electrodes 20.000 V
NOTE
Igniter box (black
connector cover)
only in combination
with control unit
1572
Igniter electrodes 20.000 V
NOTE
Igniter box
(green connector cover;
mechanically coded)
in combination with
control unit
1572D and
also with
control unit
1572
2500
3000
8
8,5
9
9,5
10
10,5
11
4000
5000
6000
7000
8000
8500
Thermo 350
Thermo 300/301
Thermo 230/231
Speed (min
-1
)
Pump pressure in relation to speed
Pu
m
p p
re
ssu
re
(b
a
r)
Summary of Contents for thermo 231
Page 2: ......
Page 10: ...1 Introduction Thermo 230 231 300 301 350 104 Page empty for notes...
Page 26: ...4 Technical Data Thermo 230 231 300 301 350 404...
Page 50: ...7 Circuit Diagrams Thermo 230 231 300 301 350 712...
Page 72: ...10 Packaging Storage Shipping Thermo 230 231 300 301 350 1002 Page empty for notes...
Page 73: ...Thermo 230 231 300 301 350 Annex A A 1 Annex A Scheduled Maintenance...