You are now ready to configure the unit using the
System Parameter table below.
*S03 setting 1 is used for Control Group options 2 and 3 see pages 33 - 36,
communication connection must be used, global heat/cool changeover is also included
if applicable to your system.
**S03 setting 0 is used for option 1 (see page 31) when heat/cool changeover is
required for individual PRTs, communication connections must be used for this function.
S03 setting 0 is only available if setting 0 has been selected for S01. If no heat/cool
changeover is required when using PRTs only then select setting 2 for S03.
28
JGSTAT2 Instruction Manual
Installation - System Parameters
SX
FUNCTION
SYSTEM
DEFINITION
DEFAULT
SETTING
System Unit
0
Programmable Room Stat (PRT)
SO1
Type
1
Digital Thermostat
0
2
HW Timer
0**
PRT only with communication*
System
1*
Group Control Thermostat and
S03
Communication
Group Thermostat communication
1
2
No Communication /
Grouping required