Chapter 1: Module Overview
1-3
User’s Manual Pub. 0300309-01 Rev. B
Table 1-1. Output/Performance/Environmental Requirements
Output Description
Value
Operating Temperature
-20 ºC to 65 ºC (-4 ºF to 149 ºF)
Storage/Non-Operating
Temperature
-40 ºC to 85 ºC (-40 ºF to 185 ºF)
Operating Humidity
5% to 95%, non-condensing
Storage/Non-Operating Humidity
5% to 85%, non-condensing
Vibration/Operating
10 Hz to 500 Hz, 2 G, 0.030 max peak-to-peak
Operating Shock
25 G, peak acceleration, 11 ms pulse, half sine
Storage/Non-Operating Shock
25 G peak acceleration, (35 G for panel mount), 11 ms pulse,
half sine
Pollution Level
Meets Pollution Degree 2 requirements.
Outputs per module
32
12/24 VDC customer supply
voltage
10.5 VDC minimum, 30 VDC maximum
ON-state voltage
10 VDC minimum ON under all conditions
24 VDC nominal under all conditions
30 VDC maximum
ON-State Voltage Drop
Less than 0.5 VDC maximum
ON-state current
1 mA minimum at 10 VDC
0.5 A maximum steady state (8 A per channel group)
Off-state leakage current
Less than 0.5 mA per channel.
Turn on/off time, maximum
(backplane to screw)
3 ms
Surge current
2 A for 25 ms, repeatable every 2 seconds
10 A maximum per channel group
Reverse voltage protection
Yes, group protection
Inductive kickback protection
Yes. Diode across load to protect against load coil back EMF.
Output to backplane isolation
50 VAC working Reinforced isolation tested at 2 kVDC for 1
minute
Group-to-Group isolation
50 VAC working Basic isolation tested at 1300 VDC for 1
minute.
Output to Chasis GND isolation
50 V working Reinforced isolation tested at 2 kVDC for 1
minute.
Power Requirements
Bus +5 VDC (4.75 V to 5.4 V)
70 mA maximum
Bus +24 VDC (19.9 V to 26.4 V)
55 mA maximum