Chapter 3:
Configuring the Micro800 Expansion I/O 2085-O
X
32-SC Using CCW
3-11
User’s Manual Pub. 0300309-01 Rev. B
The following example shows module hardware errors in CCW version 12:
3.6.2
Module Specific Configuration Errors
If you attempt to set the fields in the configuration file to invalid (unsupported)
values, the module generates a non-critical error:
•
The CCW connection status is faulted
•
The module is disconnected as Offline mode
If any of the following faults has happened, look up the Configuration Table to
use appropriate values:
Fault Code
Extended Fault
Code
Error Description
0×F2Bz
0×400
General Channel Configuration Error
No additional information
0×410 – 0×417
Configuration error on Invalid Connection Method
Connection Method selection error. Valid selections are 2-wire,
3-wire with compensation, and 4-wire.
0×430 – 0×437
Invalid Process Alarm and Latching
The selected Process Alarm option is out of the valid selectable
range.
0×440 – 0×447
Invalid Process Alarm Value
Check the Process Alarm Low Value and Process Alarm High
Value for legal ranges. If the module receives any of the
following illegal data, this error is detected:
PALV greater than or equal to PAHV
PAHV greater than Input Type High Limit
PALV less than Input Type Low Limit
PALV is the Process Alarm Low Value
PAHV is the Process Alarm High Value
The extended configuration fault code is not available and will be displayed as
4
z indicates the slot number of the expansion I/O. If z=0, then the slot number cannot be identified.