A-2
Appendix A: Module Specifications
Owner’s Guide 0300199-01 Rev. D
Specification
Description
Operating Temperature
0 °C to 60 °C (32 °F to 140 °F)
Storage Temperature
-40 °C to 85 °C (-40 °F to 185 °F)
Relative Humidity
5% to 95% (without condensation)
Certification
CE, UL, and CUL approved
Voltage Range AC 50 mVpp
AC 200 mVpp
5 VDC
12/24 VDC
VIL
-50 mV
-200 mV
1 V
6 VDC
VIH
+50 mV
+200 mV
3.5 V
10.5 VDC
Vmax CE
±50 VAC rms
±50 VAC rms
±50 VDC
±50 VDC
Input Range
Max Frequency Min Duty Cycle Max Duty
Cycle
Min Pulse
Width
AC (50 mV)
65 kHz
NA
NA
NA
AC (200 mV)
65 kHz
NA
NA
NA
5 VDC
65 kHz
30
60
4.6 usec
12 VDC
65 kHz
35
70
5.4 usec
24 VDC
65 kHz
25
55
3.8 usec
Current Range
4 mA maximum at 50 VDC
Input impedance
Resistance
Voltage-dependent greater than 1 Mohm at 5 V,
24 Kohm typical at 24 V
Capacitance
600 pF typical
Counter Speed
0 to 65 kHz Input Frequency 0 to 65 kHz
Counter Gate Input:
VIL
VIH
Vmax
1.0 V minimum
3.5 V maximum
30 V
Min/Max Duty Cycle
Channel Update Time:
With scaling
13 ms for all 8 channels
Summary of Contents for 1756-CTR8
Page 1: ...Owner s Guide 0300310 02A...
Page 8: ...viii ControlLogix CTR8 Counter Module Owner s Guide 0300199 01 Rev D...
Page 12: ...1 4 Chapter 1 Module Overview Owner s Guide 0300199 01 Rev D...
Page 44: ...5 10 Chapter 5 Configuration Data and Status Tags Owner s Guide 0300199 01 Rev D...
Page 50: ...6 6 Chapter 6 Programming Examples Owner s Guide 0300199 01 Rev D...
Page 58: ...8 4 Chapter 8 Maintaining Your Module and Ensuring Safety Owner s Guide 0300199 01 Rev D...
Page 68: ...I 2 Index Owner s Guide 0300199 01 Rev D...
Page 69: ...Owner s Guide 0300199 01 Rev D...