Owner’s Guide 0300199-01 Rev. D
Chapter 7
Troubleshooting
The count module has indicators which provide indication of module status.
ControlLogix modules use the following:
LED
This display:
Means
Take this action:
OK
Steady Green Light
The inputs are being
multicast
None
OK
Flashing Green Light The module has passed
internal diagnostics but
is not currently
performing connected
communication
None
OK
Flashing Green Light The module has passed
internal diagnostics but
is not currently
performing connected
communication
None
OK
Flashing Red Light
Previously established
communication has
timed out.
Check controller
OK
Steady Red Light
It is likely the module
should be replaced
See below
Under fault conditions the CTR8 will communicate a particular error via a LED
blink code. A description of the fault conditions and LED blink codes is listed
below:
OK LED
SYS LED
Fault Status
RED
1 Blink
EEPROM seed completed.
RED
2 Blinks
EEPROM seed failed.
RED
3 Blinks
EEPROM CRC failed.
RED
4 Blinks
Invalid serial number.
RED
5 Blinks
Boot code CRC failed.
RED
6 Blinks
App CRC failed.
RED
7 Blinks
FPGA configuration fail.
Summary of Contents for 1756-CTR8
Page 1: ...Owner s Guide 0300310 02A...
Page 8: ...viii ControlLogix CTR8 Counter Module Owner s Guide 0300199 01 Rev D...
Page 12: ...1 4 Chapter 1 Module Overview Owner s Guide 0300199 01 Rev D...
Page 44: ...5 10 Chapter 5 Configuration Data and Status Tags Owner s Guide 0300199 01 Rev D...
Page 50: ...6 6 Chapter 6 Programming Examples Owner s Guide 0300199 01 Rev D...
Page 58: ...8 4 Chapter 8 Maintaining Your Module and Ensuring Safety Owner s Guide 0300199 01 Rev D...
Page 68: ...I 2 Index Owner s Guide 0300199 01 Rev D...
Page 69: ...Owner s Guide 0300199 01 Rev D...