Owner’s Guide 0300199-01 Rev. D
Appendix A
Module Specifications
This appendix lists the specifications for the 1756sc-CTR8 Counter Module.
Specification
Description
Backplane Current Consumption
230 mA at 5 VDC 75 mA at 24 VDC
Backplane Power Consumption
3.00 W maximum (0.6 W at 5 VDC,
2.4 W at 24 VDC)
Maximum Power Dissipation
4.8 W (All inputs at maximum
voltage)
Number of Channels
8 unidirectional/4 bi-directional and
quadrature
Number of Gates
8 gate inputs
I/O Chassis Location
Any I/O module slot
Conversion Method
FPGA
Input Filtering
Three user-selectable filters (12 kHz,
25 kHz, debounce)
Calibration
Module does not require calibration
Input Overvoltage Protection
±50 VDC
Input Overcurrent Protection
Less than 4 mA at 50 VDC
Isolation
2550 VDC continuous between inputs
and chassis ground, and between
inputs and backplane.
Specification
Description
LED Indicators
1 red/green status indicators, 1 red
system status
Recommended Cable
Shielded twisted pair extension wire
Belden 8761 or equivalent shielded
Belden 9501
Maximum Wire Size
One 2.1 mm
2
(16 AWG) wire per
terminal
Summary of Contents for 1756-CTR8
Page 1: ...Owner s Guide 0300310 02A...
Page 8: ...viii ControlLogix CTR8 Counter Module Owner s Guide 0300199 01 Rev D...
Page 12: ...1 4 Chapter 1 Module Overview Owner s Guide 0300199 01 Rev D...
Page 44: ...5 10 Chapter 5 Configuration Data and Status Tags Owner s Guide 0300199 01 Rev D...
Page 50: ...6 6 Chapter 6 Programming Examples Owner s Guide 0300199 01 Rev D...
Page 58: ...8 4 Chapter 8 Maintaining Your Module and Ensuring Safety Owner s Guide 0300199 01 Rev D...
Page 68: ...I 2 Index Owner s Guide 0300199 01 Rev D...
Page 69: ...Owner s Guide 0300199 01 Rev D...