IR3 Flame Detector User Guide
Note:
When using the FS-1100 to activate the 20/20MI-3x flame
detector models the reflector will need to be disconnected (figure 1, item
5) by unscrewing the three fixing screw using an Allen wrench (3mm)
and point the simulator towards the detector from a close distance, as
shown in image 1.
Please note that the detector should be set on any sensitivity other than
2.5m. It is recommended setting the detector to the highest sensitivity
of 10m prior to the test.
Figure 8: Using FS-1100 with the
SharpEye MI-3
Figure 9: FS-1100 reflector
7.5
Safety Precautions
After power-up, the detector requires almost no attention in order to
function properly, but the following should be noted:
•
Follow the instructions in the manual and refer to the drawings and
specifications issued by the manufacturer.
•
Do not expose the detector to radiation of any kind unless required for
testing purposes.
•
Do not open the detector housing while the power is on.
•
Do not touch internal parts other than the 3 functional switches.
Interference with internal circuits may impair detector performance and
will invalidate the SPECTREX warranty.
•
Disconnect external devices, such as automatic extinguishing systems,
before carrying out any maintenance.
Item 5