False Alarms Detection
24
SharpEye
TM
IR3 Flame Detector User Guide
3.3
False Alarms Detection
The detector does not provide an alarm or a warning signal as a reaction to
the radiation sources specified in Table 5.
Table 5: Immunity to False Alarm Sources
Radiation Source
Immunity
Distance
ft/m
Sunlight
IAD
Indirect or reflected sunlight
IAD
Incandescent frosted glass light, 100 W
IAD
Incandescent clear glass light, rough service, 100W
IAD
Fluorescent light with white enamel reflector, standard office or
shop, 40W (or 2 20W)
IAD
Electric arc [12mm /
15/32”
gap at 4000V alternating current, 60Hz] IAD
Arc welding [4mm / 5/32
”
rod; 240A]
Ambient light extremes (darkness to bright light with snow, water,
rain, desert glare, and fog)
IAD
Bright colored clothing, including red and safety orange.
IAD
Electronic flash (180 watt-seconds minimum output)
IAD
Movie light, 625W quartz DWY lamp (Sylvania S.G.-55 or equivalent) 6.5/2
Flashlight (MX 991/U)
IAD
Radiation heater, 1500W
IAD
Radiation heater, 1000W with fan
IAD
Quartz lamp (1000W)
10/3
Mercury vapor lamp
IAD
Grinding metal
IAD
Lit cigar
1/0.3
Lit cigarette
1/0.3
Match, wood, stick including flare up
10/3
Notes:
•
IAD = Immune at Any Distance
•
All sources are chopped from 0
–
20Hz