Detector Mode Setup
TM 787100 Rev (Af), May 2019
31
Table 12: Time Delay
Delay (seconds)
0
A (anti-flare)
3 (default)
5
10
15
20
30
Note:
The FM approval does not allow use of 20 and 30 second setting
delay.
4.3.4
Function Setup
You can select the desired mode of operation by means of the host.
Table 13: Function Setup
Name
Yes
No
Alarm Latch
Alarm latching enable
Alarm latching disabled
(default)
Automatic BIT
Automatic & manual BIT
(default)
Manual BIT only
Alarm BIT
Successful Manual BIT
activates the alarm relay for
approximately 3 seconds; the
4
–
20mA will provide 15mA for
3sec
Successful manual BIT does
not activate the alarm relay
(default)
4.3.5
Addresses Setup
Refer to
TM 784050
for instructions for defining the addresses of the
detectors.
The detector provides up to 247 addresses (from 1 to 247) that can be used
with the RS-485 communications link.
4.3.6
Detector Default Setup
The detector has 5 functions that can be programmed according to the
customer requirement at the factory or at the customer facility using the
software host. Table 14 lists the standard setup (default) that the detector
is programmed with if there are no specific requirements.