GB
10
necessary combustion air pipes are open during the operation of the fireplace
insert. Simultaneous operation with a ventilation system (e.g. extractor hood,
bathroom fan, etc.) in the same room or connected space can adversely affect
the function of the stove (to the point of smoke or flue gas accumulating in the
living room, despite the firebox door being closed). It is therefore prohibited
to operate appliances of this kind simultaneously with a fireplace without first
taking appropriate precautionary measures („2.3.2.3 Room-air-independent“).
2.3.2.2 SEPARATE COMBUSTION AIR SUPPLY
The stove can be supplied with combustion air separately. The separate com-
bustion air connection can be connected to the rear side or from below. The
connecting piece is preassembled and the cladding must be opened accord-
ingly. When connecting a pipe connection to the combustion air neck, the
combustion air can be supplied to the stove from the outside or from other
rooms such as the cellar. When connecting the stove to a combustion air line,
the TROL instructions (technical rules), the DIN 18896, etc. must be observed
and applied.
In particular, ensure that the dimensions of the pipes are adequate!
When using the rotary base, the connection must be designed as
durable and flexible! The ability for it to rotate must not be affected.
The combustion air openings and lines must not be closed or blocked other than
if it has been ensured that the fireplace can only be operated with opened fas-
tening by special safety equipment. The cross-section must
not
be narrowed by a
fastening or a grille. This measure is not necessary with LAS chimneys. A shut-off
valve must be installed, where the combustion air feed line runs outside the build-
ing. In doing so, it must be possible to easily determine the shut-off valve setting
from outside of the connecting line. In this version, the pipe should be insulated
to prevent condensation. The pipe should be positioned, so that any condensation
formed can run out of the pipe and any water or other foreign substances from
outside cannot get into the stove. In accordance with regulations, combustion
air piping crossing a fire wall in buildings with more than two storeys must be
established in such a manner that smoke or fire cannot be transmitted to other
floors or fire compartments. Country-specific and local fire safety regulations
must be observed!
SPARTHERM QUICK COUPLING - SQC COUPLING
Compatible with the following stoves:
• Senso S
• Piko / Cubo S/M/L
• Passo XS
• Passo S/M/L
• Redoro S/M
The installation location of the stove must be determined according to the
specified technical data for the supply channel / hole. For direct wall mount-
ing, the combustion air and flue gas connection must be prepared on one
level. The stove is delivered with the fitted SQC coupling and the adjustable
feet extended. In this condition, the connecting piece is in the air, and there
is no contact to base unit. Therefore, the stove can be transported as usual
with the normal tools (e.g. sack truck).