21
POSSIBLE CAUSE
VERIFICATION
SOLUTION
Incorrect Low Voltage Connections
Check low voltage connections
Correct low voltage connections.
against wiring diagram.
Loose Low Voltage Connections
Check all wiring connections for
Tighten all loose connections.
tightness.
Defective Blower Relay
Check relay as described on page 23
If defective, replace relay.
in this manual.
Defective Blower Motor
Check motor as described on page
If defective, replace motor.
23 in this manual.
CONDITION: ESP-V UNIT WILL NOT START, BUT CONDENSING UNIT CYCLES
POSSIBLE CAUSE
VERIFICATION
SOLUTION
Blower Motor
Check motor as described on page 23
If defective, replace motor.
in this manual.
Check motor amps and compare to
If excessive, the motor may be
nameplate ratings.
overloaded. Check supply duct for
breaks or leaks.
CONDITION: ESP-V UNIT CYCLES, BUT CONDENSING UNIT RUNS
POSSIBLE CAUSE
VERIFICATION
SOLUTION
Anti-Frost Switch & Float Switch.
Thermostat fan ON. With volt meter,
If no voltage, fan relay is defective.
Switches Are Wired in
check for 24v across terminal G on
Replace it.
Series.
the fan relay and terminal C on low
If read 24v, relay is O.K.
voltage terminal strip.
With volt meter, check for 24v at
If no voltage, check coil for ice and
terminals YT and YC on the low voltage drain pan for excessive water. If ice
terminal block.
check air filter, return air duct &
blower motor for air flow. If
excessive water check and clean
condensate drain lines.
If no ice on coil and water level in
drain pan is normal, check each
switch for continuity. If switch has
no continuity, replace it
If 24v, switches are O.K.
Thermostat in Wrong Location
Check that thermostat is in vicinity of
If necessary, relocate thermostat.
return air box.
Loose Low Or High Voltage Wiring
Check all wiring connections for
Tighten all loose connections.
tightness.
Defective Blower Motor
Check motor as described on page 23. If defective, replace motor.
in this manual.
Condensing Unit
Refer to manufacturer’s instructions.
Repair or replace per manufacturer’s
instructions.
CONDITION: ESP-V UNIT RUNS, BUT CONDENSING UNIT CYCLES