Installation & Adjustment Procedures 

 

operator will have to be changed to achieve proper rotation.  

Please contact representative.

 

3.  Leave the operator in the starting position as originally shown on the operating mechanism 

drawing. 

4.  To achieve CLOCKWISE handle rotation to OPEN you must attach the adjustable arm 180 

degrees from its original setup.  The pipe clevis will also need to be rotated to the opposite 

side of the adjustable arm (side closest to the structure) but with the radius of the clevis 

still pointing toward the disconnect switch.  The adjustable arm will now rotate toward the 

structure instead of away from it. 

5.  Attach all other items as shown in the operating mechanism drawing. 
6.  If the mechanism was originally setup for PUSH to OPEN it has now been changed to 

PULL to OPEN and vice versa. 

5  Horizontally mounted disconnect switches with EVG-1 ground switch –  PARTIAL 

DISASSEMBLY WILL BE REQUIRED.  Please contact Local Representative or Southern 

States Service Division immediately.  

New brackets for the ground switch and a new 

main switch operator will be required to make this change.

 

5.1 Disconnect adjustment 

5.1.1  With the disconnect phase on the ground, remove the ground switch 

and mounting bracket as a complete assembly. 

5.1.2  If the insulators have not been installed, unbolt the live parts from the 

switch bearings and flip the paddle arms on each bearing along the 

long axis of the switch base.  Reinstall all items as described in section 

1. 

5.1.3  If the insulators have been installed, unbolt the male and female blades 

from the insulator.  Unbolt the insulators from the switch bearings and 

flip the paddle arms on each bearing along the long axis of the switch 

base.  Reinstall all items as described in section 1. 

5.1.4  Minor adjustments maybe required to the operating rod (Refer to Error! 

Reference source not found.) to achieve proper open close operation 

as described in Section 2 above. 

5.2 Ground Switch Adjustment 

5.2.1  Rotate the ground switch jaw 180 degrees and reattach to disconnect 

blade. 

5.2.2  Install new support bracket to the switch base.  The ground switch 

must be installed on the OPEN side of the disconnect.  Adjust the 

jacking bolts on the bracket until ground switch fits properly into its jaw. 

5.3 Operator and Operating linkage adjustment 

5.3.1  Both operators must move to the opposite leg(s) of the structure 

directly across from their current position 

5.3.2  Operator 

  Setup operating linkages as shown in revised operating mechanism drawings 

that will be provided. 

  Please note that a new operator will be needed for the main switch.  The ground 

switch operator is the same. 

 

Summary of Contents for COLE L

Page 1: ...COLE TYPE L Copper Center Break Disconnect Switch For 8 3 72 5 kV Ratings INSTRUCTION INSTALLATION MANUAL...

Page 2: ...Page I The Quality Name in High Voltage Switching...

Page 3: ...Page II The Quality Name in High Voltage Switching Safety Information...

Page 4: ...his manner will constitute the Warranty Holder s exclusive remedy and fulfillment of all SSLLC s liabilities and responsibilities hereunder SSLLC s duty to perform under this limited warranty may be d...

Page 5: ...Page IV The Quality Name in High Voltage Switching Southern States LLC Equipment Receipt Installation Use Operation and Maintenance Terms Terms of Use...

Page 6: ...Page V The Quality Name in High Voltage Switching...

Page 7: ...Page VI The Quality Name in High Voltage Switching Type L 8 3 72 5 kV...

Page 8: ...al Disconnect Switch 4 Receiving Handling Storage 5 Unpacking 5 Storage 5 Installation Adjustment Procedures 6 Recommended Tools Values 6 Preferred Switch Assembly Method 7 Operating Mechanism 9 Final...

Page 9: ...mmended Installation and Maintenance Table 16 Figures Page Figure 1 Type L 69kV 1600 amp 4 Figure 2 Insulator Attachment 7 Figure 3 Mounting Live Parts 7 Figure 4 Blade Clearance A B 8 Figure 5 Typica...

Page 10: ...ire obligations of Southern States The Warranty contained in the contract between the parties is the sole warranty of Southern States Any statements contained herein do not create new warranties or mo...

Page 11: ...uthern States LLC in the event conditions associated with a specific application are not sufficiently addressed All photographs and sketches in this manual are for illustration purposes only and may n...

Page 12: ...ting kV 8 3 15 5 27 38 48 3 72 5 BIL kV 95 110 150 200 250 350 ADDITIONAL RATINGS Rated Power Frequency 60 Hz Continuous Current 1200A 2000A Short Time Symmetrical Withstand 3 Sec 38 kA RMS 50 kA RMS...

Page 13: ...g the insulators F to the switch base A Mounting the live parts B to the insulators Mounting the switch base A to the structure Installing operating mechanism components Final adjustment or tuning A S...

Page 14: ...ontact the factory Storage All components of the Cole Type L center break disconnect switch are suitable for outdoor use Keep bearings out of standing water Keep upright and support live parts with ba...

Page 15: ...rocedures Recommended Tools Values Table 2 Recommended Tools and Torque Values Recommended Tools Recommended Torque Values Type Sizes Bolt Nut size Torque Ft lb Hand Wrenches and or Sockets 15 16 3 4...

Page 16: ...ference Exception Vertically mounted switches should always be assembled on the ground When assembling the switches on the ground so not attempt to make contact adjustments until the switch is mounted...

Page 17: ...ds 7 Check the main pivot bolt on the live part hinge to make sure it is tight 8 Manually test operate checking for proper contact engagement The blade should enter the jaw centrally with equal cleara...

Page 18: ...ure 5 Figure 5 Typical Operating Arrangement 3 Caution The pipe collar above the vertical bearing must support the entire weight of the vertical operating pipe To prevent unnecessary component damage...

Page 19: ...inue tuning the other two phases one at a time 2 Switch Operating Devices 2 1 Worm gear operator HOGO High Output Geared Operator Optional 2 1 1 The operator handle is factory set to rotate clockwise...

Page 20: ...7 Type SEGO Safety Enhanced Gear Operator 3 3 Electrical motor operator 3 3 1 Please refer to motor operator instruction manual for proper installation and setup 3 3 2 Use manual operation while comp...

Page 21: ...If the switch is fully open before the operator reaches the fully open position the adjustable arm radius is too long Close the switch match mark the adjustable arm and the pipe clevis and loosen the...

Page 22: ...Refer to Table 2 5 9 2 Apply a minimal amount of grease to the point of each piercing bolt and then tighten the bolt until it pierces the pipe wall For heavy walled pipe schedule 80 or above 3 or abov...

Page 23: ...gonally from its original location This is the best option as it allows for the original setup to be maintained 1 3 2 Maintain the operator on the same side of the structure Assemble the components us...

Page 24: ...and mounting bracket as a complete assembly 5 1 2 If the insulators have not been installed unbolt the live parts from the switch bearings and flip the paddle arms on each bearing along the long axis...

Page 25: ...es on the switches which can be eliminated during normal switch maintenance Table 3 Recommended Installation and Maintenance Table Installation Tests Patrolling Inspection 6 months Routine 5 Year Peri...

Page 26: ...se during any operation or maintenance cycle as exposed surfaces such as contacts are vulnerable to environmental conditions and contaminants that can decrease the effectiveness of the grease over tim...

Page 27: ......

Page 28: ...orgia Avenue Hampton Georgia 30228 Phone 770 946 4562 Fax 770 946 8106 E mail support southernstatesllc com http www southernstatesllc com 2021 Southern States LLC IB 107 Cole L Rev6 02182021 Printed...

Reviews: