background image

BrewBlast™ 70CPH O&M                                                              

 

 

         

    South-Tek Systems 

        

16 

 

6.

 

Once in 

“Standby” mode, wait 60 seconds. After 60 seconds, the system should remain in “standby” 

mode. If it doesn’t, the leak is somewhere between the check valve and the output ball valve on the 
tank. 

7.

 

If the system remains in standby, contact your local distributor/installer for further assistance. 

4.8

 

ACCESS CONTROLS 

The built-in control timer is programmed to function without requiring the user to input any values. Do not attempt to 
modify the timing or the warranty will be voided. In case of a failure, first attempt to cycle the power to the system. If 
that does not work, please contact your provider for further instructions. 

4.9

 

STARTING THE SYSTEM 

To start the system, turn on the power switch and make sure any valves to the gas lines are in the open position. 

 

4.10

 

STOPPING THE SYSTEM 

To  stop  the  system,  close  off  any  valves  on  the  gas  lines.  Powering  down  the  system  is  not  necessary.  If 
emergency shut off is required, turn off the power switch on the side on the control panel. 

 

5

 

SYSTEM USAGE 

5.1

 

INSTRUCTIONS 

The 

BrewBlast™  70CPH  is  intended  to  be  used  to  generate  nitrogen  to  push  coffee  out  of  the  keg.  Follow  the 

installation instructions above and only use in an approved environment. The generator generates enough nitrogen 
to  push  40  pints  per  hour.  Make  sure  that  proper  regulators,  cooler  temperature,  and  line  temperatures  are 
maintained,  otherwise  you  will  not  be  able  to  effectively  push  coffee  from  the  keg.  Please  consult  with  your  local 
distributor for questions not answered in this manual.  

 

The system is designed for 24 hour operation, but routine maintenance on the filters must be performed. Reference 
the 

“System Maintenance” section for detailed maintenance instructions. 

5.2

 

ALARM NOTIFICATION 

BlastOff™ - 

Leak Detection System

 Alarm 

All 

BrewBlast™ 70CPH models come standard with the patented BlastOff™ - 

Leak Detection System

. It detects 

line leaks within the downstream gas lines from the N

2

 Generator to the kegs. Line leaks could be due to a keg 

not  being  tapped  correctly,  a  coffee  gas  line  leak  or  fitting  therein  failing,  etc.  These  leaks  are  potential  safety 
hazards,  can  cause  the  CO

2

  to  deplete  quickly,  and  could  cause  your 

BrewBlast™  70CPH  to  run  in  excess 

(decreasing the life of the unit). 

 

Once a leak has been detected, the BlastOff

™ is set to initiate a buzzer, displays “B.Off” in red on the controller 

screen,  and  shuts  off  the 

BrewBlast™  70CPH  until  the  problem  has  been  remedied.  To  reset  the  BlastOff™, 

simply  turn  off  the 

BrewBlast™ 70CPH and turn it back on. The  BrewBlast™ 70CPH can be ordered with the 

BlastOff™ System Factory installed or the system can be retrofitted in the field.  Some rewiring is required to 
field install. 

 

Never reset repeatedly; 

if the BlastOff™ goes off daily, there is a real potential issue. Consult your installer for a 

solution. The label below will be on your BrewBlast

™ BrewBlast™ 70CPH if factory installed. 

Summary of Contents for 70CPH

Page 1: ...The Leader in Nitrogen Generation Technology 70CPH Operation and Installation Manual Version 0 05 30 2019 2020...

Page 2: ...BrewBlast 70CPH O M South Tek Systems 2 VERSION HISTORY Revision Implemented By Revision Date Approved By Approval Date Reason 0 M Thomas 05 30 19 A Norman 05 30 19 Initial Release...

Page 3: ...t 70CPH 8 4 2 Electrical Requirements 8 4 3 Mounting BrewBlast 70CPH 8 4 4 Installation BrewBlast 70CPH 10 4 5 Nitrogen Cylinder Back Up BrewBlast 70CPH 14 4 6 Start Up Procedures BrewBlast 70CPH 14 4...

Page 4: ...BrewBlast 70CPH O M South Tek Systems 4 Notes...

Page 5: ...ce the unit ensure the power switch has been turned to the off position then disconnect the unit s external power cord from the building electrical power supply if possible When servicing your system...

Page 6: ...rforming any electrical work NOTE Always following local and site safety regulations in conjunction with this manual Warning This manual must be read in its entirety prior to installing and operating...

Page 7: ...e system in a Standby Mode when the tank is full of Nitrogen McDantimTM Dual Output Gas Blender optional Precisely blends N2 with CO2 from the restaurant bar s in house storage cylinder tank The avail...

Page 8: ...been read completely and all connections are made as stated within Keep all gas lines dry so that moisture does not enter the generator upon hookup Never place or stack objects on top of the BrewBlas...

Page 9: ...inet in comparison to the wall a Use the supplied nuts and bolts to attach the upper 12 bracket onto the top flange per the diagram b Use the supplied carriage bolts and nuts to attach the 18 lower br...

Page 10: ...gas to all of the beverage lines Use only quality beverage tubing and fittings for all connections Keep in mind the temperature and pressure requirements when selecting them Always install a valve on...

Page 11: ...It is the responsibility of the installer to plumb these drains to an area where standing water is trapped or a drain is located Failure to do so can cause a slipping hazard on the floor below the ge...

Page 12: ...BrewBlast 70CPH O M South Tek Systems 12...

Page 13: ...BrewBlast 70CPH O M South Tek Systems 13 Optional Separate N2 Storage Tank Setup...

Page 14: ...em is turned on the backup will fill the N2 Storage tank and flow to the BrewBlast 70CPH keeping the internal blender pressurized with Nitrogen See below for visual piping connections 4 6 START UP PRO...

Page 15: ...ally The pressure switch is preset at the factory no field adjustment is required 4 7 CHECKING FOR LEAKS When a leak is suspected first try to listen for leaks around the connection ports If a leak is...

Page 16: ...mperature and line temperatures are maintained otherwise you will not be able to effectively push coffee from the keg Please consult with your local distributor for questions not answered in this manu...

Page 17: ...ilter bowls until the filter is completely depressurized 1 Disconnect the clear blue drain tubes from the bottom of the bowls 2 To remove the bowl turn the metal casing around the blue plastic filter...

Page 18: ...the filter bracket to keep track of when the filter was replaced last 10 Put the front cover back on the cabinet and the unit can be powered up again Once powered up you should hear the air compressor...

Page 19: ...BrewBlast 70CPH O M South Tek Systems 19...

Page 20: ...have the blender option check the CO2 regulator pressure gauge It should read between 80 and 100 psig If it is lower check the CO2 Storage tank to see if it needs refilling or if the pressure regulato...

Page 21: ...s received with defects that are not due to shipping a written claim should be submitted to South Tek Systems within 1 week of receiving the shipment South Tek Systems can deny all other claims at the...

Page 22: ...BrewBlast 70CPH O M South Tek Systems 22 Last Page...

Reviews: