Chapter 5 Function parameter
81
Code
Parameter name
Setting range
Factory
default Change
E2.01 Keyboard preset STD
setting
0.0% to 100.0%
50.0%
☆
When select E2.00 = 0, that is the target source is from keyboard setting, you need to
set this parameter.
The reference value for this parameter is the amount of system feedback.
E2.02 STD feedback source
selection
Analog channel AI1
feedback
0
0
☆
Analog channel AI2
feedback
1
Panel potentiometer
feedback
2
AI1-AI2 feedback
3
Remote communications
feedback
4
AI1 + AI2 feedback
5
MAX (|AI1|,|AI2|)
6
MIN (|AI1|,|AI2|)
7
This parameter is used to select the STD feedback channel.
Note: the setting channel and the feedback channel can not overlap, or, STD can not be
effectively controlled.
E2.03 STD output selection
STD output as positive
0
0
☆
STD output as negative
1
STD output as positive, when the feedback signal is greater than STD setting, the
inverter output frequency is required to drop in order to balance STD. Such as winding
tension STD control.
STD output as negative, when the feedback signal is greater than STD setting, the
inverter output frequency is required to rise in order to balance STD. Such as
unwinding tension STD control.
E2.04 Proportional gain (KP)
0.00 to 100.00
1.00
☆
E2.05 Integration time (Ti)
0.01 to 10.00s
0.10s
☆
E2.06 Differential time (Td)
0.00 to 10.00s
0.00 s
☆