Chapter 5 Function parameter
77
Code
Parameter name
Setting range
Factory default Change
obvious, conversely, the effect of oscillation suppression is very week.
Fb.05 Amplitude limit value of
oscillation suppression
0 to 10000
5000
☆
The large voltage boost value of oscillation suppression can be restricted by setting
Fb.05
Fb.06
Demarcation frequency of high
and low frequency of oscillation
suppression
0.00Hz to F0.08
(maximum
output
frequency)
12.50Hz
☆
Fb.06 is the demarcation point of function code Fb.03 and Fb.04.
Fb.07 Oscillation suppression
Oscillation
suppression valid 0
1
☆
Oscillation
suppression
invalid
1
The oscillation suppression is for VF control, the current oscillation phenomena often
occurs when the ordinary motor runs with light load or no load, which can cause
abnormal operation of motor or even the overcurrent of inverter. When Fb.07 = 0, the
oscillation suppression will be enabled;the inverter will suppress the oscillation of
motor according to the parameters of Fb.03 to Fb.06 function group.
Fb.08 PWM selection
PWM mode 1
0
0
★
PWM mode 2
1
PWM mode 3
2
PWM mode 1: V/F control is less than 8Hz as the seven-stage type, greater than 12Hz
as the five-stage type.
PWM mode 2: V/F control fully uses the seven-stage type.
PWM mode 3: V/F control fully uses the five-stage type.
Fb.09 Energy-saving selection
OFF
0
0
★
Auto energy-
saving
1
When the motor runs at constant speed with no load or light load, the inverter detects
the load current, adjusts the output voltage, in order to automatically save energy.
Fb.10 Deadband time
2 to 5
Depends on
models
5-2-14.E0 Group - Wobbulate control group