![Sourcetronic 60961 User Manual Download Page 40](http://html1.mh-extra.com/html/sourcetronic/60961/60961_user-manual_1336349040.webp)
Chapter 5 Function parameter
34
No. Code
Parameters
Setting range
Factory
default Change
Reference
page
value.
BIT10 to BIT15:
Reserved
97.
F6.03 Speed display
coefficient
0.1 to 999.9%
100.0%
☆
66
98.
F6.04 to
F6.07
Reserved
5-1-9.F7 Group - Auxiliary function
No. Code
Parameter name
Setting range
Factory
default Change
Reference
page
99.
F7.00 Jog running frequency
0.00 to F0.08
(maximum
output
frequency)
5.00Hz
☆
67
100.
F7.01 Jog running
acceleration time
0.1 to 3600.0s
Depends
on models
☆
67
101.
F7.02 Jog running
deceleration time
0.1 to 3600.0s
Depends
on models
☆
67
102.
F7.03 Acceleration time 2
0.1 to 3600.0s
Depends
on models
☆
67
103.
F7.04 Deceleration time 2
0.1 to 3600.0s
Depends
on models
☆
67
104.
F7.05 Jump frequency
0.00 to F0.08
(maximum
output
frequency)
0.00Hz
☆
67
105.
F7.06 Jump frequency range
0.00 to F0.08
(maximum
output
frequency)
0.00Hz
☆
67
106.
F7.07
Jump frequency
availability during
ac/deceleration process
0: Invalid
1: Valid
0
☆
68
107.
F7.08 Forward/reverse
rotation deadband
0.0 to 3600.0s
Depends
on models
☆
68
108.
F7.09 Power terminals
running protection
0: Power
terminals
0
☆
69